    Current Rating  
   
 

 

However for installations conditions other than above current rating factors incorporated in IS 3961 Part-Il may please be applied.

The following points should be taken into consideration before selecting any particular size & type of cable:

1 The system of power & voltage source where the cable are being used.
2 Conditions of installation at site.
3 Current carrying capacity of cable.
4 Voltage drop of the cable.
5 Short circuit capacity of cable.
6 Availability of the selected size of cable.
Formula for calculating the Short Circuit for other durations
It =
    Where......
I1 = Short Circuit Current for one second.
It = Short Circuit fort t seconds.
t = Duration in second.
Maximum Conductor temperature during short circuit is 160 C for PVC and HR PVC Cables.
 
HP KW Single Phase Amp Three Phase Amp Recommended Cable Size Sq mm.
0.5 0.37 3.7 1.0 1.5 Copper
0.75 0.55 5.0 1.3 1.5 Copper
1.0 0.75 6.5 1.9 1.5 Copper
1.5 1.10 11.5 2.6 1.5 Copper
2.0 1.50 --- 3.7 1.5 Copper
3.0 2.20 --- 4.8 1.5 Copper
5.0 3.70 --- 7.8 1.5 Copper
7.5 5.50 --- 11.2 1.5 Copper
10.0 7.50 --- 15.5 2.5 Copper
12.5 9.30 --- 19.0 2.5 Copper
15.0 11.00 --- 22.0 6 Aluminium
20.0 15.00 --- 29.0 10 Aluminium
25.0 18.50 --- 35.0 16 Aluminium
30.0 22.00 --- 40.0 16 Aluminium
35.0 26.00 --- 47.0 25 Aluminium
40.0 30.00 --- 53.0 25 Aluminium
50.0 37.00 --- 65.0 35 Aluminium
60.0 45.00 --- 80.0 50 Aluminium
75.0 55.00 --- 94.0 70 Aluminium
100.0 75.00 --- 127.0 95 Aluminium
125.0 90.00 --- 152.0 150 Aluminium
           
 
 
BENDING RADIUS

The Following Minimum bending radius should be observed for Ashocab CABLE in order that the cables, specially insulation, may not get damage in installation

  Single Core Ashocab Cable --15 X D
Multi Core Ashocab Cable --15 X D
                               Where D is the overall diameter of cable.
RECOMMENDED PULLING FORCE
(a) When conductor pulled by pulling eye:
(i) Aluminium Conductor Cable (Newton) -- 30 X Total conductor area in sq.mm.
(ii) Cupper Conductor Cable (Newton) -- 50 X Total conductor area in sq.mm.
(b) When cable pulled with stocking :
(i) Unarmoured cable 1.1K. V. (Newton) -- 5 X D2
(ii) Armoured cable 1.1K. V. (Newton) -- 9 X D2
  Where D is the overall diameter of cable.
 
 
 
 